Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.18 - Restricted opening of car or hoistway doors 2.12.5 Restricted Opening of Hoistway or Car Doors (Re-Inspection) x Door restrictor is mechanical type. Found to be out of adjustment on several floors. Repair as needed. 12/3/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.5 Illumination of Pits The elevator pit light did not work on the day of inspection, repair for proper illumination of the pit floor. 3/29/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.5 Illumination of Pits The pit light fixtures failed to illuminate in the pit. Repair pit light fixtures to provide lighting of not less than five foot candles at the pit floor for maintenance & emergency personnel. 3/29/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.3.1.6(h) Phase 2 Audible/Visual Signal (Re-Inspection) x The fireman's emergency service phase I and II operations was tested and the following deficiency was noted:- The audible signal device did not sound when phase I was activated. Reinspection is required. 2/6/2024
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A copy of the current operating certificate shall be displayed in the machine room 3/29/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.23 - Suspension rope 8.11.2.1.3(cc)(3) Replace when diameter is reduced (Re-Inspection) x Hoist ropes showing rouge. Measured, found to be undersized. Replace 12/3/2020
conversion conversion n/a FULL LOAD INSPECTION - ISSUE CERTIFICATE, CHANGE 5 YR. DATE 9/18/2017