Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.3.1.6(h) Phase 2 Audible/Visual Signal (Re-Inspection) x The fireman's emergency service phase I and II operations was tested and the following deficiency was noted: - The audible signal device did not sound when phase I was activated. Reinspection is required. 2/6/2024
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A copy of the current operating certificate shall be displayed in the machine room 3/29/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.3 - Operating control devices 8.11.2.1.1(c) On car COP, hoistway access switch and independent service function not enabled. Repair 11/16/2020
A17.1-2016 : Elevators 2.12 - Controller Wiring, Fuses, Grounding, Etc. 8.11.2.1.2(q) Found red untagged fire service wires hanging in controllers. Unit was installed in "02, but note on wall says upgraded '07. Determined if wires are part of elevator system and tag accordingly. 11/16/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 8.6.4.7 Cleaning of Pits Provide means to prevent accumulation of fluids in pit. 11/16/2020
conversion conversion conversion - reinspect x Emergency phone shall work. 9/18/2018
conversion conversion n/a FULL LOAD TEST 9/17 9/18/2017