Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
conversion conversion n/a FEO panel needs to have a lock 7/1/2018
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.6 - Ventilation 8.11.2.1.2(f) Repair/replace air conditioner and remove air handler from machine room. 11/16/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.2 - Car top light and outlet 2.14.7 The car top inspection light/fixture did not operate. Repair light/fixture for proper operation and illumination for maintenance/emergency personnel. 3/29/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.5 - Car lighting and receptacles 2.14.7.4 Protection of Light Bulbs and Tubes The cab ceiling is of the open type, which does not provide protection from the light bulbs should they shatter. The lights shall be guarded by plastic sleeve or some other means to properly protect passengers. 3/29/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.4 - Top-of-car Clearance, Refuge Space, & Standard Railing 2.14.1.7 Railing and Equipment on Top of Cars A supplemental safety hand rail has been added to the top of the elevator car that strikes the deflector sheeve at the top of the hoistway when the elevator travels up to its full travel. The handrail is now disfigured and shall be re-fabricated to not strike the deflector sheeve to the clearances in accordance to A17.1 2004a. No red tag issued as this condition has been present for an undetermined amount of time. 3/29/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6 General Maintenance Methods Independent Service operation is not functioning at the time of inspection and shall be repaired to operate as designed. 3/29/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates Hoistway landing Braille floor identification tags are missing on multiple floors and shall be reinstalled. The identification tags are required for passengers and emergency personnel in an emergency. 3/29/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.2-2.27.8 x x Cab fire service buzzer inoperative. Did NOT red tag. 10/17/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 11 CSR 40-5.090 Inspection and Testing 8.11 Periodic Inspection and Test. x Incomplete Cat 5 testing. 9/28/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 11 CSR 40-5.090 Inspection and Testing 8.11 Periodic Inspection and Test. x Car failed to recover after counterweight buffer test. Reinspect to complete the Cat 5 test. 12/2/2020