ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.5 - Housekeeping
|
8.11.2.1.2(e) (Re-Inspection)
|
|
|
Equipment and materials not related to the operation or maintenance of the elevator shall not be stored in the elevator machine room.
|
4/26/2022
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
8.11 Periodic Inspection and Test.
|
x
|
|
Could not perform the relief valve verification of setting and system pressure test. The relief pressure shall be tested and obtained.
|
4/26/2022
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.11 - Plunger and Cylinder
|
8.6.5.8 Safety Bulkhead
|
x
|
|
Need to determine if this unit is a single bottom jack. Take corrective action if unit is confirmed to be a single bottom jack. If unit is determined to be double bottom type then documentation shall be kept on-site in the machine room.
|
4/26/2022
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.5 - Housekeeping
|
8.11.2.1.2(e) (Re-Inspection)
|
|
|
The machine room shall be cleaned of dirt and excessive amount of dust.
|
4/26/2022
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A current MO State operating certificate shall be obtained and displayed in the elevator machine room.
|
9/18/2023
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.41 - Maintenance Records
|
8.6.1.4
|
|
|
A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room.
|
9/18/2023
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.7 - Car door or gate
|
8.11.2.1.1(g)
|
|
|
The car gate will not operate when the open or close button is activated.
|
9/18/2023
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.16 - Rated load, platform area, and data plate
|
8.11.2.1.1(p)
|
|
|
Install a loading class plate conspicuously on the elevator car.
|
9/18/2023
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.8 - Pipes, wiring, and ducts
|
8.11.2.1.2(h)
|
|
|
Machine rooms that have pipes carrying liquids, gas, or vapors that cross overhead of the elevator equipment or come in close proximity of the equipment shall be guarded or guttered.
|
9/18/2023
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.1 - Access to machine space
|
8.11.2.1.2(a)
|
|
|
All room enclosures shall have a self-closing and self-locking door and shall be operable from the interior space without the use of a key.
|
9/18/2023
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.11 - Disconnecting Means and Control
|
2.26.4
|
|
|
The disconnect located in the machine room shall be provided with a sign to identify the location of the supply side overcurrent protective device.
|
9/18/2023
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.33 - Tanks
|
8.11.3.1.2(p)
|
|
|
The hydraulic tank drip pan has an excessive amount of oil, it shall be cleaned.
|
9/18/2023
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.1 - Access to machine space
|
8.11.2.1.2(a)
|
|
|
The entrance to the machine room shall be maintained in a clear and unobstructed manner. The boxes and pallets obstructing the machine room entry shall be removed.
|
9/18/2023
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.7 - Car door or gate
|
8.11.2.1.1(g)
|
|
|
The car gate will not operate when the open or close button is activated.
|
9/18/2023
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.16 - Rated load, platform area, and data plate
|
8.11.2.1.1(p)
|
|
|
Install a loading class plate conspicuously on the elevator car.
|
9/18/2023
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.3 - Lighting and receptacles
|
8.11.3.1.2(c)
|
|
|
The lighting in the machine room shall not be less than 10 foot candles measured at the floor. Increase the lighting.
|
9/18/2023
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.8 - Pipes, wiring, and ducts
|
8.11.2.1.2(h)
|
|
|
Machine rooms that have pipes carrying liquids, gas, or vapors that cross overhead of the elevator equipment or come in close proximity of the equipment shall be guarded or guttered.
|
9/18/2023
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.1 - Access to machine space
|
8.11.2.1.2(a)
|
|
|
All room enclosures shall have a self-closing and self-locking door and shall be operable from the interior space without the use of a key.
|
9/18/2023
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.41 - Maintenance Records
|
8.6.1.4
|
|
|
Written evacuation procedures for elevators by authorized persons and emergency personnel shall be available on-site.
|
9/18/2023
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.41 - Maintenance Records
|
8.6.1.4
|
|
|
A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022)
|
9/18/2023
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.11 - Disconnecting Means and Control
|
2.26.4
|
|
|
The disconnect located in the machine room shall be provided with a sign to identify the location of the supply side overcurrent protective device.
|
9/18/2023
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
8.6.4.7 Cleaning of Pits
|
|
|
Clean the pit of dirt, debris, and oil.
|
9/18/2023
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.1 - Access to machine space
|
8.11.2.1.2(a)
|
|
|
The entrance to the machine room shall be maintained in a clear and unobstructed manner. The boxes & pallets obstructing the machine room entry shall be removed.
|
9/18/2023
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
2.2.3 Guards Between Adjacent Pits
|
|
|
Remove the oil and water from the pit.
|
9/18/2023
|