Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x Emergency alarm must be operational 8/16/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records Compliant/Required Documentation & MCP shall be kept in equipment room(neat/organized) including Wiring Diagrams, Oil log &Fire service log, recorded monthly. (Provided by Elev Co.) 4/19/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) x Emergency lighting not working, 8/30/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - Door Systems 8.6.4.13 (Re-Inspection) x G(1) /8.6.4.13 / 2.13.5/ 2.26: Detector edge shall work with Cab lighting circuit disconnected 8/30/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) x Emergency lighting not working, 8/30/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - Door Systems 8.6.4.13 (Re-Inspection) x G(1) /8.6.4.13 / 2.13.5/ 2.26: Detector edge shall work with Cab lighting circuit disconnected 8/30/2022
MO Minimum : Elevators (I) - Pits (I)1 Pit steel rusted, clean. Paint. Monitor. 4/19/2023
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) Pit light does not work 7/2/2020
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 106.1e Illumination of Pits I-1 Mo-min dampness in pit, sump cover needs to be replaced 7/25/2019
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Display current state operating certificate 8/14/2023