Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Elevators that are equipped to operate on emergency power shall be tested with no load in the car while operating on the emergency generator. 6/8/2023
MO Minimum : Elevators (F) - Electrical Switches (F)2 x x Top final limit does not stop elevator while in flight. The limit switch shall be repaired and tested. 3/19/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements x The car top stop switch does not stop elevator while in flight. The switch shall be repaired and tested. 3/19/2020
MO Minimum : Elevators (I) - Pits (I)7 x The pit stop switch does not stop the elevator while in flight. The pit stop switch shall be repaired and tested. 3/19/2020