Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 1.17 - Standby power operation 8.11.2.1.1(q) Yes No Elevators that are equipped to operate on Emergency Power shall be tested operating on Em Power,
A17.1-2016 : Elevators 1.6 - Car emergency signal 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No Buildings over 60ft require a a two-way voice communication means within the building accessible to emergency personnel aka "Rescue Phone"
A17.1-1996 : Elevators 1.6 - Car emergency signal 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No Two-way communication device shall give proper location, message, full address & unit number. 9/28/2023
A17.1-1996 : Elevators 1.6 - Car emergency signal 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No Emergency communication/phone in car is not working. 10/3/2024
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No Testing incomplete. Fire service, Phase 1 & 2 need to be tested. 9/28/2023
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No Testing incomplete. Fire service, Phase 1 & 2 need to be tested. 8/26/2024
A17.1-2016 : Elevators 2.10 - Numbering of Elevators, Machines, Controllers, and Disconnect Switches 8.10.2.2.2(o) Yes No Mainline and Lighting disconnects shall be labeled with Elevator number, location of feeder breakers, and function
A17.1-2016 : Elevators 2.4 - Machine space 8.6.4.8 Machine Room and Machinery Space Yes No door shall be self-closing and self-locking and proper fire rating. Currently a sheet of plywood is acting as the door for construction.
A17.1-2016 : Elevators 2.4 - Machine space 8.6.4.8 Machine Room and Machinery Space Yes No Lighting shall not be less than 200lux/19fc at floor in front of controller.
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 No No The MCP, including PM records and monthly fire service test log are not being properly documented. 2/24/2026
A17.1-1996 : Elevators 2.7 - Fire Extinguisher 1206.1h No No An ABC fire extinguisher with a current test tag shall be mounted convenient to the machine room door. 11/10/2022
A17.1-1996 : Elevators 2.7 - Fire Extinguisher 1206.1h No No Update fire extinguisher in machine room 12/21/2022
A17.1-1996 : Elevators 3.1 - Top-of-car stop switch 1001.2(c)(1) No No Replace broken stop switch on elevator car top. 11/4/2020
A17.1-1996 : Elevators 3.23 - Suspension rope 212 Yes No Hoisting ropes failed gauge test, need to be replaced. 10/3/2024
A17.1-2016 : Elevators 3.34 - Earthquake Inspection and Tests (Seismic Risk Zone 2 or Greater) 8.6.4.19.17 Earthquake Operation Yes No SEISMIC- Ring&String was removed during the MOD, Reinstall and test.
A17.1-2016 : Elevators 4.12 - Standby power selection switch 8.6.4.19.7 (Re-Inspection) Yes No Emergency power selector switches/car swap and Lobby panel functions shall be tested
A17.1-2016 : Elevators 4.5 - Access to Hoistway 8.6.4.14 Hoistway Access Switches Yes No Test Hoistway access switches once installed
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.8 Switch Keys Yes No Test Phase 1 hall switch for function, once installed.
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 1206.7 No No A record of findings for firefighters' service operation required by 8.6.11.1 with identification of the person(s) that performed the operation shall be kept on site. 11/10/2022
conversion conversion conversion - reinspect Yes No Emergency phone not working due to bad phone line. Reinspect. 8/23/2018
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. 11/10/2022
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. 2/24/2026