Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 3.1 - Top-of-car stop switch 1001.2(c)(1) Replace broken stop switch on elevator car top. 11/4/2020
A17.1-1996 : Elevators 2.7 - Fire Extinguisher 1206.1h Update fire extinguisher in machine room 12/21/2022
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. 11/10/2022
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 1206.7 A record of findings for firefighters' service operation required by 8.6.11.1 with identification of the person(s) that performed the operation shall be kept on site. 11/10/2022
A17.1-1996 : Elevators 2.7 - Fire Extinguisher 1206.1h An ABC fire extinguisher with a current test tag shall be mounted convenient to the machine room door. 11/10/2022
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 The MCP, including PM records and monthly fire service test log are not being properly documented.
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
A17.1-1996 : Elevators 3.23 - Suspension rope 212 x Hoisting ropes failed gauge test, need to be replaced. 10/3/2024
conversion conversion conversion - reinspect x Emergency phone not working due to bad phone line. Reinspect. 8/23/2018
A17.1-1996 : Elevators 1.6 - Car emergency signal 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Two-way communication device shall give proper location, message, full address & unit number. 9/28/2023
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Testing incomplete. Fire service, Phase 1 & 2 need to be tested. 9/28/2023
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Testing incomplete. Fire service, Phase 1 & 2 need to be tested. 8/26/2024
A17.1-1996 : Elevators 1.6 - Car emergency signal 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Emergency communication/phone in car is not working. 10/3/2024