A17.1-1996 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
No
|
No
|
A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
|
11/10/2022
|
|
A17.1-1996 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
No
|
No
|
A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
|
2/24/2026
|
|
A17.1-1996 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
1206.7
|
No
|
No
|
A record of findings for firefighters' service operation required by 8.6.11.1 with identification of the person(s) that performed the operation shall be kept on site.
|
11/10/2022
|
|
A17.1-1996 : Elevators
|
2.7 - Fire Extinguisher
|
1206.1h
|
No
|
No
|
An ABC fire extinguisher with a current test tag shall be mounted convenient to the machine room door.
|
11/10/2022
|
|
A17.1-2016 : Elevators
|
1.6 - Car emergency signal
|
2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
Yes
|
No
|
Buildings over 60ft require a a two-way voice communication means within the building accessible to emergency personnel aka "Rescue Phone"
|
|
|
A17.1-2016 : Elevators
|
2.4 - Machine space
|
8.6.4.8 Machine Room and Machinery Space
|
Yes
|
No
|
door shall be self-closing and self-locking and proper fire rating. Currently a sheet of plywood is acting as the door for construction.
|
|
|
A17.1-2016 : Elevators
|
1.17 - Standby power operation
|
8.11.2.1.1(q)
|
Yes
|
No
|
Elevators that are equipped to operate on Emergency Power shall be tested operating on Em Power,
|
|
|
A17.1-1996 : Elevators
|
1.6 - Car emergency signal
|
211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
Yes
|
No
|
Emergency communication/phone in car is not working.
|
10/3/2024
|
|
conversion
|
conversion
|
conversion - reinspect
|
Yes
|
No
|
Emergency phone not working due to bad phone line. Reinspect.
|
8/23/2018
|
|
A17.1-2016 : Elevators
|
4.12 - Standby power selection switch
|
8.6.4.19.7 (Re-Inspection)
|
Yes
|
No
|
Emergency power selector switches/car swap and Lobby panel functions shall be tested
|
|
|
A17.1-1996 : Elevators
|
3.23 - Suspension rope
|
212
|
Yes
|
No
|
Hoisting ropes failed gauge test, need to be replaced.
|
10/3/2024
|
|
A17.1-2016 : Elevators
|
2.4 - Machine space
|
8.6.4.8 Machine Room and Machinery Space
|
Yes
|
No
|
Lighting shall not be less than 200lux/19fc at floor in front of controller.
|
|
|
A17.1-2016 : Elevators
|
2.10 - Numbering of Elevators, Machines, Controllers, and Disconnect Switches
|
8.10.2.2.2(o)
|
Yes
|
No
|
Mainline and Lighting disconnects shall be labeled with Elevator number, location of feeder breakers, and function
|
|
|
A17.1-1996 : Elevators
|
3.1 - Top-of-car stop switch
|
1001.2(c)(1)
|
No
|
No
|
Replace broken stop switch on elevator car top.
|
11/4/2020
|
|
A17.1-2016 : Elevators
|
3.34 - Earthquake Inspection and Tests (Seismic Risk Zone 2 or Greater)
|
8.6.4.19.17 Earthquake Operation
|
Yes
|
No
|
SEISMIC- Ring&String was removed during the MOD, Reinstall and test.
|
|
|
A17.1-2016 : Elevators
|
4.5 - Access to Hoistway
|
8.6.4.14 Hoistway Access Switches
|
Yes
|
No
|
Test Hoistway access switches once installed
|
|
|
A17.1-2016 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
2.27.8 Switch Keys
|
Yes
|
No
|
Test Phase 1 hall switch for function, once installed.
|
|
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
Yes
|
No
|
Testing incomplete. Fire service, Phase 1 & 2 need to be tested.
|
9/28/2023
|
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
Yes
|
No
|
Testing incomplete. Fire service, Phase 1 & 2 need to be tested.
|
8/26/2024
|
|
A17.1-1996 : Elevators
|
2.41 - Maintenance Records
|
8.6.1.4
|
No
|
No
|
The MCP, including PM records and monthly fire service test log are not being properly documented.
|
2/24/2026
|
|
A17.1-1996 : Elevators
|
1.6 - Car emergency signal
|
211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
Yes
|
No
|
Two-way communication device shall give proper location, message, full address & unit number.
|
9/28/2023
|
|
A17.1-1996 : Elevators
|
2.7 - Fire Extinguisher
|
1206.1h
|
No
|
No
|
Update fire extinguisher in machine room
|
12/21/2022
|