Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x 1.5 Emergency light needs battery 2/28/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements Remove oil pads and oil from pump drip pan.
MO Minimum : Elevators (I) - Pits (I)1 Pit shall be kept clean and dry. Remove oil soaked pads and clean oil spillage.
MO Minimum : Elevators (I) - Pits (I)1 I(1)/106.1 Pit shall be kept clean and dry. Remove oil soaked pads and clean oil spillage.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records G(1)/8.6.1.4 : MCP shall be kept in equipment room, including Fire service testing log, recorded monthly. no MCP on-site.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records Compliant/Required Documentation & MCP shall be kept in equipment room(neat/organized) including Wiring Diagrams, Oil loss log and Fire service testing log, recorded monthly
conversion conversion n/a set test elevator dropps due to oil leakage in valve components needs rebuilt or replaced 7/24/2018