MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4 Maintenance records
|
|
|
No records
|
11/4/2021
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.7 Signs and Data Plates
|
|
|
Phase II halo not ledge able
|
11/4/2021
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)8
|
|
|
Could not locate cab light disconnect
|
11/4/2021
|
MO Minimum : Elevators
|
(S) - Fire Service
|
8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection)
|
x
|
|
Phase II key would not work
|
10/21/2021
|
conversion
|
conversion
|
n/a
|
|
|
Standing 15 min test elevator dropped 5 1/4", did same test with pit valve shut off, elevator dropped 1/16"--valve needs to be rebuilt or replaced
|