Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.2.5 Sump Pump Required/Capacity (Re-Inspect) Yes No no sump pump 8/8/2024
MO Minimum : Elevators (S) - Fire Service 8.6.11.1 Monthly Test and Log No No 2020 log for monthly fire service test not filled out 3/24/2021
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)8 Car Lighting No No one of the cab ceiling lights is burnt out, not meeting the 5 foot-candle illumination inside the cab 3/24/2021
MO Minimum : Elevators (S) - Fire Service 8.6.11.1 Monthly Test and Log No No monthly fire service test log is not being filled out monthly. 9/1/2023
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)8 Car Lighting No No the cab ceiling lights did not come back on after turning off the 110 volt breaker to test the emergency lights. 9/1/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) No No does not have Maintenance Control Program documents in the machine room 9/1/2023
MO Minimum : Elevators (S) - Fire Service 8.6.11.1 Monthly Test and Log No No monthly fire service test log is not being filled out monthly 9/1/2023
MO Minimum : Elevators (S) - Fire Service (S)1 Yes Yes fire service phase 1 did not work from the keyswitch activation or from simulating smoke detector activation (ELEVATOR RED TAGGED) 9/4/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) Yes No replace burnt out emergency light bulb, only one light bulb came on 8/18/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) Yes No replace emergency light battery, it is dead 8/18/2020