Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.11 - Disconnecting Means and Control 2.26.4 x NFPA 70--620.51 needs lockable disconnect for cab lighting/fan 12/9/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x telephone has yet to be programed--will not work 12/9/2019
A17.1-2016 : Elevators 1.18 - Restricted opening of car or hoistway doors 8.11.2.1.1(r) x Repair door restrictor 11/3/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.19 - Car Ride 8.11.2.1.1(s) x In down direction it was noted that once in a while the elevator had a vibration the cause needs to be identified and corrected 12/9/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.3 - Lighting and receptacles 8.11.2.1.2(c) x Needs a GFCI in machine room 12/9/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.8 - Pipes, wiring, and ducts 8.11.2.1.2(h) x relocate drain pipe from cooler so it does not go over elevator controller 12/9/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.10 - Numbering of elevators, machines, and disconnect switches 8.11.2.1.2(j) x # of disconnects, controller & car top 12/9/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.17 - Standby power operation 8.11.2.3.5 x standby power still needs to be inspected 5/8/2020