ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.17 - Standby power operation
|
8.11.2.1.1(q)
|
x
|
|
emergency power will be tested at later time when their system is corrected/time set when all 3 mods can be tested
|
12/3/2019
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.2 Headroom
|
8.11.2.1.2(b)
|
x
|
|
machine room clearances/ concrete structural beam between pump unit & controller measures 71 1/2" required by NEC 78" variance required
|
12/3/2019
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.2 Headroom
|
8.11.2.1.2(b)
|
|
|
Building concrete beam between pump unit and controller in machine room-clearance 71 1/2"--110.26(A)(3) NEC requires 78"--variance required
|
6/1/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.2 Headroom
|
8.11.2.1.2(b)
|
|
|
Headroom clearance (71 1/2") beam variance will need to be requested
|
6/1/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.3 - Lighting and receptacles
|
8.11.2.1.2(c)
|
x
|
|
additional lighting needs to be added to machine room
|
12/3/2019
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
6.2 - Operation of elevators under fire and other emergency conditions (A17.1-1981 through A17.1b-1983)
|
8.11.2.2.6
|
x
|
x
|
Shunt trip did not work --Reinspect required
|
12/3/2019
|
A17.1-2016 : Elevators
|
1.17 - Standby power operation
|
8.7.2.28
|
x
|
|
Eleveator faulted out upon transfer from normal to emergency power
|
2/5/2021
|