MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6 General Maintenance Methods
|
|
|
This elevator is not connected to the emergency generator, but there is a hall station and emergency power indicator jewel that need to be removed before the next annual inspection.
|
8/21/2023
|
MO Minimum : Elevators
|
(S) - Fire Service
|
(S)1
|
x
|
|
Elevator recalls, but phase 2 emergency fire service does not work. Fire service shall be repaired and tested.
|
11/13/2019
|
MO Minimum : Elevators
|
(S) - Fire Service
|
(S)1
|
x
|
x
|
Phase 2 fire service shall be operational.
|
1/21/2020
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Elevators that are equipped to operate on emergency power shall be tested with no load in the car while operating on the emergency generator.
|
6/8/2023
|
conversion
|
conversion
|
conversion - reinspect
|
x
|
|
Phase 2 Fire Service is not operational.
|
10/5/2018
|