MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
No
|
No
|
current cirt. not displayed
|
8/10/2026
|
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)2
|
No
|
No
|
macnine. room door not self closing or self locking
|
8/10/2026
|
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
No
|
No
|
no current cirt. displayed
|
8/10/2026
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.5 Fire Extinguishers
|
No
|
No
|
no fire extinquisher in mach. room
|
8/10/2026
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4.1(a) On-Site Maintenance Records (MCP Records)
|
No
|
No
|
no on site maint records
|
8/10/2026
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.2.2(a) On-Site Documentation (Up-to-Date Wiring Diagrams)
|
No
|
No
|
no wiring dia on site
|
8/10/2026
|
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
No
|
No
|
Repair the emergency phone
|
6/16/2022
|
|
A17.1-2016 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
8.6.4.7 Cleaning of Pits
|
No
|
No
|
pit has oil covering floor
|
8/10/2026
|
|
A17.1-2016 : Elevators
|
2.36 - Hydraulic Cylinders
|
8.6.5.5.2 Collection of Oil Leakage
|
No
|
No
|
remove oil return lines from jack to tank in machroom an put them in buckets in the pit
|
8/10/2026
|
|
A17.1-2016 : Elevators
|
2.36 - Hydraulic Cylinders
|
8.6.5.5 Gland Packing and Seals
|
Yes
|
No
|
excessive leakin replace packing
|
8/10/2026
|
|
A17.1-2016 : Elevators
|
2.31 - Relief Valves
|
8.6.5.14.1
|
Yes
|
No
|
unable to perform test
|
|