Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No Post a new copy of the state operating certificate in the elevator machine room every year 2/11/2021
MO Minimum : Elevators (S) - Fire Service 8.6.11.1 Monthly Test and Log No No Perform monthly fire service test and post the log in the machine room 2/20/2020
MO Minimum : Elevators (S) - Fire Service 8.6.11.1 Monthly Test and Log No No monthly fire service test log is not posted in the machine room, perform fire service test monthly and keep a test log in the machine room 1/27/2022
MO Minimum : Elevators (I) - Pits (I)8 No No Pit sump hole needs cover 3/7/2024
MO Minimum : Elevators (I) - Pits (I)1 No No Pit full of water. Remove and complete annual inspection. 5/28/2026
MO Minimum : Elevators (H) - Machine Rooms (H)5 (Machine Room Lighting) No No Below 10 foot candles 3/7/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers No No Machine room fire extinguisher out of date 3/7/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) Yes No emergency phone had a dial tone but could not complete the call 12/19/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) Yes No emergency light and bell battery is dead, replace the battery 12/13/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates No No In case of fire don't use elevator signage needed 3/7/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) Yes No replace missing hoistway door pick up rollers on all floors 2/4/2019
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements No No Fire caulk all penetrations in the machine room walls to maintain the fire rating of the room, new holes have been made that were not fire caulked 2/11/2021