MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.7 Signs and Data Plates
|
|
|
In case of fire don't use elevator signage needed
|
3/7/2024
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)5 (Machine Room Lighting)
|
|
|
Lighting below 10 foot candles
|
3/7/2024
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.5 Fire Extinguishers
|
|
|
Fire extinguisher out of date
|
3/7/2024
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)8
|
|
|
Sump hole needs cover
|
3/7/2024
|
MO Minimum : Elevators
|
(S) - Fire Service
|
8.6.11.1 Monthly Test and Log
|
|
|
monthly fire service test log is not posted in the machine room, perform fire service test monthly and keep a test log in the machine room
|
1/27/2022
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Post a new copy of the state operating certificate in the elevator machine room every year
|
2/11/2021
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 Maintenance, Repair and Replacements
|
|
|
Fire caulk all penetrations in the machine room walls to maintain the fire rating of the room, new holes have been made that were not fire caulked
|
2/11/2021
|
MO Minimum : Elevators
|
(S) - Fire Service
|
8.6.11.1 Monthly Test and Log
|
|
|
Perform monthly fire service test and post the log in the machine room
|
2/20/2020
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)8 Car Lighting
|
|
|
replace cab light bulbs, dos not meet the minimum illumation of 5 foot candles (50 Lux) at the threshold with the doors closed
|
2/20/2020
|