Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) x Auxiliary power lowering is not working. Re-inspection required 4/23/2024
A17.1-1996 : Elevators 1.17 - Standby power operation 1002.2g (Standby Power Operation) x Needs 2 wires from disconnect to controller. The 2 wires needed are from an auxilliary set of contacts in the disconnect, going to the plug on controller. This lets the controller know if the disconnect is powered down or that the electric is off. Re-inspection is required
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.5 Code Data Plate Provide a code data plate conforming to sec 8.9 12/6/2021