Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No Up to date operating certificate required in machine room. 3/2/2023
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No Elevators that are equipped to operate on emergency power shall be tested with no load in car while operating on the emergency generator. 1/20/2023
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No Elevators that are equipped to operate on emergency power shall be tested with no load in the car while operating on the emergency generator. 1/16/2023
MO Minimum : Elevators (H) - Machine Rooms (H)2 No No Pipes conveying liquid, gas, or vapor that cross overhead of the elevator equipment or come in close proximity of the equipment shall be guarded or guttered. 3/2/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6 General Maintenance Methods No No The missing ceiling tiles shall be replaced in the elevator machine room. 3/2/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records No No A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) 3/2/2023