Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.23 - Suspension rope 8.11.2.1.3(cc)(1) Wire ropes shall be replaced Yes Yes Suspension ropes rouged, replace.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.26 - Broken rope, chain, or tape switch 8.11.2.1.3(i) Yes Yes SOS switch working, just worn from age, replace.
MO Minimum : Elevators (G)2-Alterations 8.7.2.14.2 Car Enclosure Yes No Emergency phone working, but not providing a location address. 11/16/2020
MO Minimum : Elevators (G)2-Alterations 8.7.2.14.2 Car Enclosure Yes No Alarm bell not working. 11/16/2020
MO Minimum : Elevators (H) - Machine Rooms (H)4 No No Remove all trash, debris, and non elevator related items from machine room, and keep clear. 1/22/2024