MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.5 Fire Extinguishers
|
|
|
Fire Extinguisher in Controller Room and Machine Room is due to be serviced or replaced
|
10/27/2022
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.13 - Door systems
|
|
|
Hoistway Door Unlocking Device at bottom landing needs to have a lockable cover to allow only authorized personnel to enter the hoistway
|
10/27/2022
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.7 Signs and Data Plates
|
|
|
Provide Phase I Fire Service instructions at Phase I Keyswitch at bottom landing
|
10/27/2022
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days)
|
x
|
|
The Emergency Phone in the car fails to establish two-way communication.
|
10/17/2024
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.2 - Bottom clearance, runby, and minimum refuge space
|
8.6.4.11
|
x
|
|
Hoist ropes have stretched reducing Runby by more than maximum allowable amount. Runby should be at least 6 inches
|
10/4/2022
|