Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.13 - Door systems Hoistway Door Unlocking Device at bottom landing needs to have a lockable cover to allow only authorized personnel to enter the hoistway 10/27/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x The Emergency Phone in the car fails to establish two-way communication. 10/17/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers Fire Extinguisher in Controller Room and Machine Room is due to be serviced or replaced 10/27/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates Provide Phase I Fire Service instructions at Phase I Keyswitch at bottom landing 10/27/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.2 - Bottom clearance, runby, and minimum refuge space 8.6.4.11 x Hoist ropes have stretched reducing Runby by more than maximum allowable amount. Runby should be at least 6 inches 10/4/2022