MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
|
|
Alarm bell and Emergency light do not work when 110 AC is removed
|
10/27/2021
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.5 Fire Extinguishers
|
|
|
Fire Extinguisher in Machine Room is due to be serviced or replaced
|
10/27/2022
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.13 - Door systems
|
|
|
Hoistway Door Unlocking Device at bottom landing needs to have a lockable cover to allow only authorized personnel to enter the hoistway
|
10/27/2022
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
8.6.5.16.5 Over Speed Valve Testing (Re-Inspect)
|
x
|
|
Overspeed valves, where provided, shall be inspected and tested to verify that they will stop the car, traveling down with rated load every 5 years.
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.7 Signs and Data Plates
|
|
|
Provide Phase I Fire Service instructions at Phase I Keyswitch at bottom landing
|
10/27/2022
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
Sump does not work. Standing water in Pit
|
10/27/2021
|