Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 8.6.4.7 Cleaning of Pits No No Sump hole is filled with oil, remove. Determine if the sump pump still works, if not replace.
A17.1-2016 : Elevators 5.15 - Overspeed Valve 8.6.5.16.5 Yes No Provide testing of the OSV.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.11 - Plunger and Cylinder 8.6.5.5 Gland Packings and Seals No No Cylinder packing is worn and leaking. Repair or replace as needed.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.18 - Restricted opening of car or hoistway doors 2.12.5 Restricted Opening of Hoistway or Car Doors (Re-Inspection) Yes No Repair the door restrictor for proper operation. Re-inspection required 6/27/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No Emergency communication not working 7/27/2023
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing (Re-Inspect) Yes No Overspeed valve not tagged. Must be cat 5 tested 7/27/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.2 - Car top light and outlet 2.14.7 No No Provide guard for car top light 10/25/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) No No A copy of the MCP shall be kept in the machine room for each unit 10/25/2025
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing (Re-Inspect) Yes No OSV is not tagged, must be Cat 5 tested. Re-inspection required 10/25/2025