Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.11 - Plunger and Cylinder 8.6.5.5 Gland Packings and Seals Cylinder packing is worn and leaking. Repair or replace as needed.
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing (Re-Inspect) x Overspeed valve not tagged. Must be cat 5 tested 7/27/2023
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing (Re-Inspect) x OSV is not tagged, must be Cat 5 tested. Re-inspection required 10/25/2025
A17.1-2016 : Elevators 5.15 - Overspeed Valve 8.6.5.16.5 x Provide testing of the OSV.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 8.6.4.7 Cleaning of Pits Sump hole is filled with oil, remove. Determine if the sump pump still works, if not replace.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) A copy of the MCP shall be kept in the machine room for each unit 10/25/2025
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Emergency communication not working 7/27/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.2 - Car top light and outlet 2.14.7 Provide guard for car top light 10/25/2025
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.18 - Restricted opening of car or hoistway doors 2.12.5 Restricted Opening of Hoistway or Car Doors (Re-Inspection) x Repair the door restrictor for proper operation. Re-inspection required 6/27/2023