Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Incomplete inspection - Fire service needs to be tested, door closing force needs to be tested. 11/9/2021
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x Phone in car works, but dials 911. Reprogram to non emergency number with 24/7 support. 9/18/2023
MO Minimum : Elevators (I) - Pits (I)1 Clean the pit. 4/17/2023
MO Minimum : Elevators (S) - Fire Service 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) x Phase II is not working. 14 days allowed to correct and re-test.