Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
conversion conversion n/a The pit shall be clean of oil and debris. 9/11/2018
conversion conversion n/a The car door roller(s) are bad. Door does not operate smoothly. 9/11/2018
conversion conversion n/a The emergency light and alarm does not work. 9/11/2018
conversion conversion n/a The emergency light and alarm does not work. 9/11/2018
conversion conversion n/a The pit shall be clean of oil and debris. 9/11/2018
conversion conversion n/a The car door roller(s) are bad. Door does not operate smoothly. 9/11/2018
A17.1-1996 : Elevators 1.6 - Car emergency signal 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x A17.1 2016 8.6.4.15 - The in car emergency telephone shall be operational. 9/23/2022
A17.1-1996 : Elevators 1.18 - Restricted opening of car or hoistway doors 111.5 Restricted Opening of Hall/Car Doors x The means to restrict opening of the car door shall be operational. 9/23/2022
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. 9/28/2023
A17.1-1996 : Elevators 1.6 - Car emergency signal 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x The emergency phone answers but hangs up. The in car emergency phone shall be operational and code compliant. 12/29/2023
A17.1-1996 : Elevators 1.17 - Standby power operation 211.2 x Elevators that are equipped to operate on emergency power shall be tested with no load in the car while operating on the emergency generator. 12/29/2023
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 211.8 Switch Keys x Keys to test fire service are not on-site. Fire service shall be tested to complete the annual inspection. All elevators in the building shall be operable by the FEO-K1 key. These keys should be on premises in a location accessible to firefighters and emergency personnel, but not to the public. 12/29/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.2.1 Repair Parts First floor hall light does not work. Control & operating devices and controls shall be maintained. 2/6/2024
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. 2/6/2024
A17.1-1996 : Elevators 3.3 - Top-of-car operating device 1001.2(c)(3) Repair damaged car top run station. - Reinspection Required 2/6/2024
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Display current state operating certificate. 2/6/2024
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 8.6.4.7 Cleaning of Pits Oil shall not accumulate on the pit floor. The pit shall be cleaned. 2/6/2024