A17.1-1996 : Elevators
|
1.6 - Car emergency signal
|
1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
A17.1 2016 8.6.4.15 - The in car emergency telephone shall be operational.
|
9/23/2022
|
A17.1-1996 : Elevators
|
3.3 - Top-of-car operating device
|
1001.2(c)(3)
|
|
|
Repair damaged car top run station. - Reinspection Required
|
2/6/2024
|
A17.1-1996 : Elevators
|
1.18 - Restricted opening of car or hoistway doors
|
111.5 Restricted Opening of Hall/Car Doors
|
x
|
|
The means to restrict opening of the car door shall be operational.
|
9/23/2022
|
A17.1-1996 : Elevators
|
1.6 - Car emergency signal
|
211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
The emergency phone answers but hangs up. The in car emergency phone shall be operational and code compliant.
|
12/29/2023
|
A17.1-1996 : Elevators
|
1.17 - Standby power operation
|
211.2
|
x
|
|
Elevators that are equipped to operate on emergency power shall be tested with no load in the car while operating on the emergency generator.
|
12/29/2023
|
A17.1-1996 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
211.8 Switch Keys
|
x
|
|
Keys to test fire service are not on-site. Fire service shall be tested to complete the annual inspection. All elevators in the building shall be operable by the FEO-K1 key. These keys should be on premises in a location accessible to firefighters and emergency personnel, but not to the public.
|
12/29/2023
|
A17.1-1996 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
|
9/28/2023
|
A17.1-1996 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Display current state operating certificate.
|
2/6/2024
|
A17.1-1996 : Elevators
|
2.41 - Maintenance Records
|
8.6.1.4
|
|
|
A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room.
|
2/6/2024
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.2.1 Repair Parts
|
|
|
First floor hall light does not work. Control & operating devices and controls shall be maintained.
|
2/6/2024
|
A17.1-2016 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
8.6.4.7 Cleaning of Pits
|
|
|
Oil shall not accumulate on the pit floor. The pit shall be cleaned.
|
2/6/2024
|
conversion
|
conversion
|
n/a
|
|
|
The pit shall be clean of oil and debris.
|
9/11/2018
|
conversion
|
conversion
|
n/a
|
|
|
The car door roller(s) are bad. Door does not operate smoothly.
|
9/11/2018
|
conversion
|
conversion
|
n/a
|
|
|
The emergency light and alarm does not work.
|
9/11/2018
|
conversion
|
conversion
|
n/a
|
|
|
The emergency light and alarm does not work.
|
9/11/2018
|
conversion
|
conversion
|
n/a
|
|
|
The pit shall be clean of oil and debris.
|
9/11/2018
|
conversion
|
conversion
|
n/a
|
|
|
The car door roller(s) are bad. Door does not operate smoothly.
|
9/11/2018
|