Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 MCP shall be kept in equipment room, including Fire service testing log, recorded monthly. 11/23/2020
A17.1-1996 : Elevators 2.8 - Pipes, wiring, and ducts 102.1 Does not conform to NFPA 70 code. An air duct is pressing against disconnect arm, not allowing for proper switching or LOTO. 11/23/2020
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Current State Operating Permit shall be displayed in the Equipment Room in a non-combustible frame. 11/23/2020