A17.1-1996 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
No
|
No
|
Current State Operating Permit shall be displayed in the Equipment Room in a non-combustible frame.
|
11/23/2020
|
|
A17.1-1996 : Elevators
|
2.41 - Maintenance Records
|
8.6.1.4
|
No
|
No
|
MCP shall be kept in equipment room, including Fire service testing log, recorded monthly.
|
11/23/2020
|
|
A17.1-1996 : Elevators
|
2.8 - Pipes, wiring, and ducts
|
102.1
|
No
|
No
|
Does not conform to NFPA 70 code. An air duct is pressing against disconnect arm, not allowing for proper switching or LOTO.
|
11/23/2020
|
|
A17.1-2016 : Elevators
|
1.17 - Standby power operation
|
8.6.4.19.7 (Re-Inspection)
|
Yes
|
No
|
Provide cat 1 testing.
|
7/15/2026
|
|
A17.1-2016 : Elevators
|
4.12 - Standby power selection switch
|
8.6.4.19.7 (Re-Inspection)
|
Yes
|
No
|
Provide cat 1 testing.
|
7/15/2026
|