ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.17 - Standby power operation
|
3.26.10 (Auxiliary Power)(Re-Inspection)
|
Yes
|
No
|
Emergency battery lowering device does not work, needs repaired. Re-inspection required
|
|
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
8.6.5.16.5 Over Speed Valve Testing
|
No
|
No
|
A17.1 - 8.6.5.16.5 OVER SPEED VALVE NOT SEALED. PERFORM THE REQUIRED 5 YR TESTING ON OR BEFORE THE NEXT INSPECTION.
|
7/1/2022
|
|
A17.1-2016 : Elevators
|
5.15.2 Unsealed Overspeed Valve
|
8.6.5.16.5 (Re-Inspect)
|
Yes
|
No
|
A17.1 - 8.6.5.16.5 OVER SPEED VALVE NOT SEALED. PERFORM THE REQUIRED 5 YR TESTING DUE IN 90 DAYS BY 5/28/2022 RE-INSPEQUIRED
|
7/1/2022
|