Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
Missouri Minimum : Escalators (T) - Existing Dumbwaiters, Escalators and Moving Walks (T)2 Bottom stop switch cover buzzer not working 1/10/2020
Missouri Minimum : Escalators (T) - Existing Dumbwaiters, Escalators and Moving Walks (T)2 Upper left handrail inlet guard needs to be replaced 1/10/2020
Missouri Minimum : Escalators (T) - Existing Dumbwaiters, Escalators and Moving Walks (T)2 lower left handrail inlet guard needs to be replaced 1/10/2020
Missouri Minimum : Escalators (T) - Existing Dumbwaiters, Escalators and Moving Walks (T)2 Bottom left lower balustrade gap exceeds maximum allowable 1/10/2020
Missouri Minimum : Escalators (T) - Existing Dumbwaiters, Escalators and Moving Walks (T)2 Demarcation lights not working 1/10/2020
Missouri Minimum : Escalators (T) - Existing Dumbwaiters, Escalators and Moving Walks (T)2(B) Replace damaged lower key up/down switch.
Missouri Minimum : Escalators (T) - Existing Dumbwaiters, Escalators and Moving Walks 8.11.4.1(e) Lighting (demarcation and step lighting) x 8.6.11.6.2(i) Step Demarcation - The top and bottom demarcation lights shall be operational. (2nd Notice)
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided. MCP shall be present and updated.
Missouri Minimum : Escalators (T) - Existing Dumbwaiters, Escalators and Moving Walks 8.6.11.5.2(i) Demarcation lighting x Top & bottom demarcation lamps shall be operational. 9/10/2021
Missouri Minimum : Escalators (T) - Existing Dumbwaiters, Escalators and Moving Walks 8.6.11.5.2(i) Demarcation lighting x Bottom demarcation lamps shall be operational. 9/10/2021
Missouri Minimum : Escalators (T) - Existing Dumbwaiters, Escalators and Moving Walks 8.6.11.6.2(i) Step Demarcation x The top and bottom demarcation lights shall be operational. 10/6/2023
Missouri Minimum : Escalators (T) - Existing Dumbwaiters, Escalators and Moving Walks 8.6.8.1 Escalator Handrails x Handrails will be free of major cracks and pinch points. Replace left handrail.
Missouri Minimum : Escalators (T) - Existing Dumbwaiters, Escalators and Moving Walks 8.6.8.2 Escalator Step-to-Skirt Clearance x The loaded step gap shall not exceed 4.8 mm on either side. (2nd Notice)
Missouri Minimum : Escalators (T) - Existing Dumbwaiters, Escalators and Moving Walks 8.6.8.2 Escalator Step-to-Skirt Clearance x The loaded step gap shall not exceed 4.8mm on either side. 10/6/2023
Missouri Minimum : Escalators (T) - Existing Dumbwaiters, Escalators and Moving Walks 8.6.8.2 Escalator Step-to-Skirt Clearance x A17.2 - 7.17 - The step indexing loaded gap shall not be greater than 4.8mm on each side. 9/10/2021
Missouri Minimum : Escalators (T) - Existing Dumbwaiters, Escalators and Moving Walks 8.6.8.2 Escalator Step-to-Skirt Clearance x 8.6.8.3 - The step/skirt performance index shall not exceed .4. 9/10/2021
Missouri Minimum : Escalators (T) - Existing Dumbwaiters, Escalators and Moving Walks 8.6.8.3 Step/Skirt Performance Index x The escalator step/skirt performance index shall not exceed .4. 10/6/2023
Missouri Minimum : Escalators (T) - Existing Dumbwaiters, Escalators and Moving Walks 8.6.8.3 Step/Skirt Performance Index x Performance index shall not exceed 0.4. (2nd Notice)