MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Elevators that are equipped to operate on emergency power shall be tested with no load in the car while operating on the emergency generator.
|
12/19/2022
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. Note: The certificate expired in 2021.
|
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(1) Minimum Standard
|
x
|
|
The auxiliary power lowering operation shall be functional.
|
10/6/2023
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
8.6.5.16.5 Over Speed Valve Testing (Re-Inspect)
|
x
|
|
The overspeed valve shall be tested with rated load. Note: The last test was in 2017.
|
10/6/2023
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(1) Minimum Standard
|
x
|
|
Relief valve setting to be adjusted above full load pressure (280 psi), not to exceed 125% of same.
|
10/9/2024
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
8.6.5.16.5 Over Speed Valve Testing (Re-Inspect)
|
x
|
|
Overspeed valve to be tested, sealed and tagged. Testing shall be completed within 90 days.
|
10/9/2024
|
MO Minimum : Elevators
|
(S) - Fire Service
|
211.3a(8) Visual and audible signal
|
|
|
Fire service buzzer and fire hat shall work correctly.
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency communications loss monitor shall work.
|
10/9/2024
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4.1(a) On-Site Maintenance Records (MCP Records)
|
|
|
Compliant/required documentation & MCP shall be kept in equipment room (neat/organized) including wiring diagrams, PM log, callback log, evacuation procedures, oil log, and fire service log, recorded monthly.
|
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
The pit shall be kept clean. Remove excess debris.
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.13 - Door systems
|
|
|
Adjust upthrust roller bearings for proper clearance to door hanger track (multiple floors).
|
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
8.6.5.16.5 Over Speed Valve Testing (Re-Inspect)
|
x
|
|
This elevator is equipped with an overspeed valve. A category 5 test shall be performed on the overspeed valve immediately. The overspeed valve was last tested in 2017. Unit will be red tagged and locked out of service if not tested.
|
12/16/2024
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
The pit shall be kept clean and free from dirt and rubbish.
|
|
MO Minimum : Elevators
|
(S) - Fire Service
|
211.3a(8) Visual and audible signal
|
x
|
|
Fire service buzzer does not work.
|
12/16/2024
|