Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
---|---|---|---|---|---|---|
A17.1-2016 : Elevators | 2.36 - Hydraulic Cylinders | 8.6.5.14.2 Hydraulic Cylinders and Pressure Piping | x | x | After the relief pressure test, while attempting to perform the 15 minute stand test, the elevator is drifting down with the shut-off valve in the pit in the closed position indicating in the ground oil loss. Identify and correct the source of oil loss. |