Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (H) - Machine Rooms (H)8 Car lighting shall be on its own designated circuit, not off the main elevator power supply
MO Minimum : Elevators (O) - Existing Hydraulic Elevators (O)4 Car failed 15 minute stand test. Oil is leaking through valve. Repair as needed and re-test. 1/12/2022
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x Emergency phone in car appears to have no line. 3/26/2024