Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
conversion conversion n/a emergency phone line is dead, provide working phone line 8/18/2020
conversion conversion n/a fire extinguisher inspection tag is from 2015, it is to be inspected annually 8/18/2020
MO Minimum : Elevators (G)2-Alterations 8.7.2.14.2 Car Enclosure x no dial tone on the emergency phone line, provide working phone line to the elevator controller 8/18/2020
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x emergency phone did not work, phone line dead 8/20/2021
MO Minimum : Elevators (S) - Fire Service 8.6.11.1 Monthly Test and Log the monthly fire service test log is not being filled out
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x emergency phone did not work, phone line is dead 9/9/2022
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)8 Car Lighting elevator cab drop ceiling has open egg crate panels, light tubes shall be guarded with tube covers to prevent breakage
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers machine room fire extinguisher inspection tag is from 2019, it is to be inspected and tagged annually
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x emergency phone did not work, Phone line is dead, provide working phone line 9/15/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers machine room fire extinguisher inspection tag is from 2019, the extinguisher is to be inspected and tagged annually
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)8 Car Lighting open egg crate drop ceiling in the elevator cab, the light tubes shall be guarded in case of accidental breakage
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.2.2(a) On-Site Documentation (Up-to-Date Wiring Diagrams) need to have a copy of the elevator wiring diagrams in the machine room
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x emergency phone did not work, phone line is dead, wires for the phone line are not even connected to the phone, provide a working phone line
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers machine room fire extinguisher inspection tag is from 2019, the machine room fire extinguisher needs to be inspected and tagged annually
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)8 Car Lighting open egg crate drop ceiling, the light tubes shall be guarded in case of accidental breakage