MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days)
|
x
|
|
emergency phone did not work, phone line dead
|
8/20/2021
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days)
|
x
|
|
emergency phone did not work, phone line is dead
|
9/9/2022
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)8 Car Lighting
|
|
|
elevator cab drop ceiling has open egg crate panels, light tubes shall be guarded with tube covers to prevent breakage
|
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)8 Car Lighting
|
|
|
open egg crate drop ceiling in the elevator cab, the light tubes shall be guarded in case of accidental breakage
|
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)8 Car Lighting
|
|
|
open egg crate drop ceiling, the light tubes shall be guarded in case of accidental breakage
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days)
|
x
|
|
emergency phone did not work, phone line is dead, wires for the phone line are not even connected to the phone, provide a working phone line
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days)
|
x
|
|
emergency phone did not work, Phone line is dead, provide working phone line
|
9/15/2023
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.2.2(a) On-Site Documentation (Up-to-Date Wiring Diagrams)
|
|
|
need to have a copy of the elevator wiring diagrams in the machine room
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.5 Fire Extinguishers
|
|
|
machine room fire extinguisher inspection tag is from 2019, the machine room fire extinguisher needs to be inspected and tagged annually
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.5 Fire Extinguishers
|
|
|
machine room fire extinguisher inspection tag is from 2019, the extinguisher is to be inspected and tagged annually
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.5 Fire Extinguishers
|
|
|
machine room fire extinguisher inspection tag is from 2019, it is to be inspected and tagged annually
|
|
MO Minimum : Elevators
|
(S) - Fire Service
|
8.6.11.1 Monthly Test and Log
|
|
|
the monthly fire service test log is not being filled out
|
|
MO Minimum : Elevators
|
(G)2-Alterations
|
8.7.2.14.2 Car Enclosure
|
x
|
|
no dial tone on the emergency phone line, provide working phone line to the elevator controller
|
8/18/2020
|
conversion
|
conversion
|
n/a
|
|
|
emergency phone line is dead, provide working phone line
|
8/18/2020
|
conversion
|
conversion
|
n/a
|
|
|
fire extinguisher inspection tag is from 2015, it is to be inspected annually
|
8/18/2020
|