Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) Yes No The in car emergency telephone shall be operational. 4/10/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.3.1 Replacement Parts No No The door operator belts are cracked and falling apart. They shall be replaced. 4/10/2024
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (1) Minimum Standard Yes No The pressure switch shall be activated by the loss of positive pressure at the top of the cylinder. The unit is equipped with a pressure switch, but the switch does not activate with loss of positive pressure as required. 6/12/2025