Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates In case of fire don't use elevator signage needed 3/9/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) x Emergency alarm bell not working 11/2/2022
MO Minimum : Elevators (H) - Machine Rooms (H)2 Machine room door needs to be self-locking 3/9/2023
MO Minimum : Elevators (H) - Machine Rooms (H)5 (Machine Room Lighting) Machine room lighting well below 10 ft candles at floor level 3/9/2023
MO Minimum : Elevators (H) - Machine Rooms (H)2 Machine room door must be self-locking 3/9/2023
MO Minimum : Elevators (O) - Existing Hydraulic Elevators (O)2(B) inconsistant relief valve pressure valve need repaired 5/19/2020