MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.5 Fire Extinguishers
|
|
|
Fire extinguisher needs to be adjacent to machine room access door.
|
9/1/2021
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.5 Fire Extinguishers
|
|
|
Mount the existing machine room fire extinguisher in proximity to access door. Fire extinguisher is presently mounted on the rear wall
|
9/1/2021
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)5 (Machine Room Lighting)
|
|
|
Increase machine room lighting. Existing machine room lighting is less than 10 ft candles at floor level.
|
9/1/2021
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
Remove debris and dead rat from elevator pit.
|
9/1/2021
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
Pit floors need to be kept dry. Standing oil on pit floor needs to be removed.
|
3/4/2019
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(1) Minimum Standard
|
x
|
|
Need to perform 5 year safety test with rated load.
|
1/14/2020
|