Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.8 Yes No wiring in hoistway not pertaning to elevator and clean pit
A17.1-2016 : Elevators 2.1 - Access to machine space 2.7.1.1 Yes No there was no door
A17.1-2016 : Elevators 2.7 - Fire Extinguisher 8.10.3.2.2(l) Yes No there wasn't a fire extiguisher
A17.1-2016 : Elevators 2.8 - Pipes, wiring, and ducts 2.8 Yes No covers missing
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.2.2(a) On-Site Documentation (Up-to-Date Wiring Diagrams) Yes No no MCP or oil log
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.2.2(a) On-Site Documentation (Up-to-Date Wiring Diagrams) Yes No no MCP or oil log
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 3.27.1 Phase I Emergency Recall Operation After Device Actuation Yes Yes tried to put in idem # 6.10 but it would not let me . All the smoke heads need to be checked for proper recall
MO Minimum : Elevators (I) - Pits (I)1 No No Pit floors need to be kept dry. Standing oil on pit floor needs to be removed. 3/4/2019
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (1) Minimum Standard Yes No Need to perform 5 year safety test with rated load. 1/14/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers No No Fire extinguisher needs to be adjacent to machine room access door. 9/1/2021
MO Minimum : Elevators (I) - Pits (I)1 No No Remove debris and dead rat from elevator pit. 9/1/2021
MO Minimum : Elevators (H) - Machine Rooms (H)5 (Machine Room Lighting) No No Increase machine room lighting. Existing machine room lighting is less than 10 ft candles at floor level. 9/1/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers No No Mount the existing machine room fire extinguisher in proximity to access door. Fire extinguisher is presently mounted on the rear wall 9/1/2021