MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.5 Fire Extinguishers
|
No
|
No
|
Fire extinguisher needs to be adjacent to machine room access door.
|
9/1/2021
|
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
No
|
No
|
Remove debris and dead rat from elevator pit.
|
9/1/2021
|
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)5 (Machine Room Lighting)
|
No
|
No
|
Increase machine room lighting. Existing machine room lighting is less than 10 ft candles at floor level.
|
9/1/2021
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.5 Fire Extinguishers
|
No
|
No
|
Mount the existing machine room fire extinguisher in proximity to access door. Fire extinguisher is presently mounted on the rear wall
|
9/1/2021
|
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
No
|
No
|
Pit floors need to be kept dry. Standing oil on pit floor needs to be removed.
|
3/4/2019
|
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(1) Minimum Standard
|
Yes
|
No
|
Need to perform 5 year safety test with rated load.
|
1/14/2020
|
|
A17.1-2016 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
2.8
|
Yes
|
No
|
wiring in hoistway not pertaning to elevator and clean pit
|
|
|
A17.1-2016 : Elevators
|
2.1 - Access to machine space
|
2.7.1.1
|
Yes
|
No
|
there was no door
|
|
|
A17.1-2016 : Elevators
|
2.7 - Fire Extinguisher
|
8.10.3.2.2(l)
|
Yes
|
No
|
there wasn't a fire extiguisher
|
|
|
A17.1-2016 : Elevators
|
2.8 - Pipes, wiring, and ducts
|
2.8
|
Yes
|
No
|
covers missing
|
|
|
A17.1-2016 : Elevators
|
2.40 - Maintenance Records
|
8.6.1.2.2(a) On-Site Documentation (Up-to-Date Wiring Diagrams)
|
Yes
|
No
|
no MCP or oil log
|
|
|
A17.1-2016 : Elevators
|
2.40 - Maintenance Records
|
8.6.1.2.2(a) On-Site Documentation (Up-to-Date Wiring Diagrams)
|
Yes
|
No
|
no MCP or oil log
|
|
|
A17.1-2016 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
3.27.1 Phase I Emergency Recall Operation After Device Actuation
|
Yes
|
Yes
|
tried to put in idem # 6.10 but it would not let me . All the smoke heads need to be checked for proper recall
|
|