Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.3.2.1 Phase 1 Emergency Recall OperationBy Fire Alarm initiating Devices x x The phase 1 fire service operation, bypass function, is not working and shall be repaired. - Violation Fixed 6/11/2020 6/11/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.2-2.27.8 x x On Phase 2 operation, the car doors shall open via constant pressure, not automatically. - Unit Red Tagged - Violation Fixed 6/11/2020 6/11/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.17 - Door and gate equipment 8.6.4.13.1(a) hoistway door Interlocks x x The hoistway door interlock contacts are worn and causing intermittent operation of the interlock on the first floor. Repair or replace for proper operation. - Violation Fixed 6/11/2020 6/11/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.18 - Restricted opening of car or hoistway doors 2.12.5 Restricted Opening of Hoistway or Car Doors (Re-Inspection) x The door restrictor is not working. Take corrective action as needed and retest. 7/25/2023