ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
2.27.2-2.27.8
|
x
|
x
|
On Phase 2 operation, the car doors shall open via constant pressure, not automatically. - Unit Red Tagged - Violation Fixed 6/11/2020
|
6/11/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.18 - Restricted opening of car or hoistway doors
|
2.12.5 Restricted Opening of Hoistway or Car Doors (Re-Inspection)
|
x
|
|
The door restrictor is not working. Take corrective action as needed and retest.
|
7/25/2023
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
3.17 - Door and gate equipment
|
8.6.4.13.1(a) hoistway door Interlocks
|
x
|
x
|
The hoistway door interlock contacts are worn and causing intermittent operation of the interlock on the first floor. Repair or replace for proper operation. - Violation Fixed 6/11/2020
|
6/11/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
2.27.3.2.1 Phase 1 Emergency Recall OperationBy Fire Alarm initiating Devices
|
x
|
x
|
The phase 1 fire service operation, bypass function, is not working and shall be repaired. - Violation Fixed 6/11/2020
|
6/11/2020
|