MO Minimum : Elevators
|
(O) - Existing Hydraulic Elevators
|
(O)4
|
|
|
8.6.12.3.7.2 jack seal needs replaced
|
9/4/2018
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.13 - Door systems
|
x
|
|
G(1)/8.6.4.13/ : Electric Eye not working
|
1/11/2023
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.5.5.2 Oil Leakage Collection
|
|
|
G/8.6.5.5.2 An oil collection reservoir needs to be repaired/replaced.
|
6/12/2023
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Must post current state operating Cert. 5.100(2)
|
7/31/2023
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.5.5.2 Oil Leakage Collection
|
|
|
Oil collection reservoir needs to be added in pit. Currently, oil leakage flows to sump.
|
8/10/2021
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.5.5.2 Oil Leakage Collection
|
|
|
Oil collection reservoir needs to be added in pit. Currently, oil leakage flows to sump.
|
9/3/2021
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
pit needs to be clean of oil and debree
|
8/27/2020
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
water,oil debree in pit pit needs to be cleaned
|
9/4/2018
|