Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 5.9 - Buffers and emergency terminal speed limiting devices 201 x x Buffer seal failed during buffer test. Elevator was removed from service until buffer is replaced and tested
A17.1-1996 : Elevators 1.5 - Car lighting and receptacles 204.7 Emergency light and alarm failed to function
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 MCP not in machine room