Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 2.43 - Emergency Brake, Ascending Car Overspeed, and Unintended Car Movement Protection 8.11.2.1.2(ii) x Devices for ascending car overspeed and unintended car movement protection shall be maintained and shall stop and hold the car, with any load up to rated load, or 125% rated load on elevators designed to carry passengers by applying an emergency brake conforming to 2.19.3. The stopped position of the car shall be limited in both directions to a maximum of 48 inches. - Elevator Red Tagged 11/24/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. 1/13/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.6 - Ventilation 8.11.2.1.2(f) The machine room temperature shall be kept within the manufacturers recommended range. 1/13/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.4 - Machine space 8.11.2.1.2(d) The missing drywall in the machine room shall be replaced. 1/13/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.6 - Ventilation 2.7.5.2 The machine room temperature shall be kept within the manufacturers recommended range. 1/13/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. 1/13/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.41 - Maintenance Records 8.6.1.4 A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) 1/13/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.2 - Car top light and outlet 2.14.7 Top of hoistway light shall be operational. 2/5/2025
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.2.6 Sump Pump Covers Sump pump needs a cover. 2/5/2025
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.2.6 Sump Pump Covers Sump pump needs a cover. Noted from previous inspection on 5/11/23. 2/5/2025
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.2.6 Sump Pump Covers Sump pump needs a cover. Noted from previous inspection on 5/11/23. 2/5/2025
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.17 - Standby power operation 8.11.2.1.1(q) x Emergency/standby power operation of the elevator shall be tested to complete the annual inspection. 11/24/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.17 - Standby power operation 8.11.2.1.1(q) x Emergency power shall be tested. 7/31/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 11 CSR 40-5.090 Inspection and Testing 8.11 Periodic Inspection and Test. x The firefighters phase 1 key-switch and jewel located in the fire command room shall be operational. Fire service has been tested and works properly, however this fire service command panel does not operate as intended. The fire service command panel shall be operational. 10/16/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.17 - Standby power operation 8.11.2.1.1(q) x Emergency power shall be tested. Building personnel were unsuccessful in transferring main elevator power over to generator power. 10/16/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.18 - Restricted opening of car or hoistway doors 2.12.5 Restricted Opening of Hoistway or Car Doors (Re-Inspection) x The means to restrict opening of the car door shall be operational. 11/24/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.17 - Standby power operation 8.11.2.1.1(q) x Emergency/standby power operation of the elevator shall be tested to complete the annual inspection. 1/13/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.9 - Buffers and emergency terminal speed limiting devices 2.22 x x Repair or replace buffers to conform to A17.2 - 5.9.1.1(b)1-6. Unit is Red Tagged. 9/14/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.2.5 Sump pump shall be provided x Repair or replace pit sump pump. The sump pump shall be operational. 9/14/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.17 - Standby power operation 2.27.2 x Elevators that are equipped to operate on emergency power shall be tested with no load in the car while operating on the emergency generator. 12/15/2023
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) A17.1 - 2004 - 1.6 - Could not establish 2-way communication. - Reinspection Required 10/9/2018
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements A17.1 - 2004 - 1.18 - Car door restrictor shall be repaired. - Reinspection Required 10/9/2018
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (1) Minimum Standard x The firefighters phase 1 key-switch and jewel located in the fire command room shall be operational. Fire service has been tested and works properly, however this fire service command panel does not operate as intended. The fire service command panel shall be operational. 7/19/2021
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (1) Minimum Standard x There is excessive rust at the bottom of both main rails and counterweight rails. Take corrective action as needed. 12/15/2023
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (1) Minimum Standard x There is excessive rust at the bottom of both main rails and counterweight rails. Take corrective action as needed. 5/1/2024