Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (S) - Fire Service 8.6.11.1 Monthly Test and Log no monthly test log 5/20/2020
MO Minimum : Elevators (S) - Fire Service (S)1 x x no smoke detector in mach room. smoke detectors in lobby an second floor an in overhead not tied to elevator cont. two sprinkler heads in mach room one heat no shunt trip 5/6/2020
MO Minimum : Elevators (H) - Machine Rooms (H)2 machine room door not self locking 5/20/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.5.5.2 Oil Leakage Collection remove hoses from cyl head to tank 7/16/2021