conversion
|
conversion
|
n/a
|
|
|
Remove emergency lights in car
|
10/24/2018
|
conversion
|
conversion
|
n/a
|
|
|
Remove oil from pit floor
|
10/24/2018
|
conversion
|
conversion
|
n/a
|
|
|
Remove oil from pit floor
|
10/24/2018
|
conversion
|
conversion
|
n/a
|
|
|
Repair emergency light in car
|
10/24/2018
|
MO Minimum : Elevators
|
(S) - Fire Service
|
(S)1
|
x
|
|
Repair Phase 2 Fire Service in car on hold will not over ride door close button
|
4/15/2019
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4 Maintenance records
|
|
|
Need a maintenance control program on site posted on controller asap
|
11/3/2021
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days)
|
x
|
|
The emergency phone shall be operational and code compliant. The answering service can not be heard.
|
12/29/2022
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)1
|
|
|
Clear the entrance to the machine room. Access to the machine space shall maintained in a clear and unobstructed manner.
|
5/8/2023
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.3.1 Replacement Parts
|
|
|
Exhaust fan is missing cover in machine room. Replace the fan cover.
|
5/8/2023
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Up to date operating certificate is required in the machine room.
|
5/8/2023
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)5 (Machine Room Lighting)
|
|
|
Guard machine room light.
|
5/8/2023
|
MO Minimum : Elevators
|
(O) - Existing Hydraulic Elevators
|
(O)4 (Re-Inspection)
|
x
|
|
Packing on jack is leaking. Take corrective action as needed.
|
3/28/2023
|
MO Minimum : Elevators
|
(S) - Fire Service
|
8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection)
|
x
|
|
Fire service phase 1 is working, but will not transfer to phase 2. Take corrective action as needed.
|
3/28/2023
|
MO Minimum : Elevators
|
(O) - Existing Hydraulic Elevators
|
(O)4 (Re-Inspection)
|
x
|
|
Packing on jack is leaking. Take corrective action as needed.
|
5/8/2023
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days)
|
x
|
|
Two-way communications device shall work.
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days)
|
x
|
|
Stop switch shall be wired to alarm for audible notification (after 1984). Front COP stop does not sound alarm.
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - Door Systems 8.6.4.13 (Re-Inspection)
|
x
|
|
Car door restrictor shall work at all floors. Multiple brackets missing.
|
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(2)(C) Re-Inspection Required to Enforce.
|
x
|
|
Cab lighting shall be a dedicated circuit. Currently on the same circuit as second floor hallway lighting/receptacles. NEC 620-22
|
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)2
|
|
|
Machine room door shall be self-closing and self-locking.
|
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
|
|
MO Minimum : Elevators
|
(S) - Fire Service
|
8.6.11.1 Monthly Test and Log
|
|
|
Fire service testing shall be documented monthy.
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.2.1 Repair Parts
|
|
|
Front door close button does not work.
|
|